ENGIE La Haute Borne, 4 x Senvion MM82 (8.2 MW), 10-minute SCADA, 2014 to 2015
464 MWh of production was lost, and two turbines account for 63 percent of it
Lost energy by driver, against 24,630 MWh produced (1.8 percent of potential).
What to act on first
Ranked by lost MWh. Reference power curves fitted on 2014 only, so 2015 is an out-of-sample year.
Performance index gap to fleet median, by month
Points of performance index (actual over expected, excluding downtime and curtailment). Outlined cells meet the persistence rule: more than 2 points from the fleet for 3 or more consecutive months.
Power curve check
2015 records (1 in 40) against the 2014 reference curve, density-normalized wind speed.
Monthly availability
Time-based availability during windy periods, per turbine.
Data quality and traceability
Every excluded record maps to one rule in sql/02_dq_flags.sql. Our downtime estimate (281 MWh) is within 9 percent of the operator's own unavailability counter (308 MWh).
Caveat: the plant meter, availability and curtailment tables are the example plant-level series distributed with NREL OpenOA, and the meter equals 0.98 of SCADA energy almost every month, so they test the reconciliation code rather than provide an independent audit.